Troubleshooting Radio Communications

If there are intermittent communication problems when connecting via radio, there may be another network in the area causing interference. To help remove the interference, useClosedDevice Configuration UtilitySoftware tool used to set up data loggers and peripherals, and to configure PakBus settings before those devices are deployed in the field and/or added to networks.to change theNetwork IDandRF Hop Sequencein all RF407, RF412, and RF422 radios within a network (standalone or included in a data logger) to another value. Each of these settings must have the same value in all radios and dataloggers within a network. For example, theNetwork IDin all devices could be set to1726, and theRF Hop Sequencein all devices could be set to1. TheNetwork ID可以是任意数字0到32767之间。的RF Hop Sequencecan be any number between 0 and 7 in an RF407 or RF412 network; it can be any number between 0 and 9 in an RF422 network.

See alsoRadio communications option. For specifications information, seeRF radio option specifications.