RF407-Series radio communications with one or more data loggers

To configure an RF407-series radio to communicate with the data logger, you must complete the following steps (instruction follows):

NOTE:

This procedure assumes the RF407 series devices are using factory default settings.

Configuring the RF407-Series radio

Configure the RF407-Series radio connected to the computer (see image inConfiguration optionsfor reference).

  1. Ensure your RF407-series radio is connected to an antenna and power.

  2. If connecting via USB for the first time, you must first install USB drivers usingDevice Configuration Utility(select your radio, then on the main page, clickInstall USB Driver). Plug the RF407-series radio to your computer using a USB or RS-232 cable.

  3. UsingDevice Configuration Utility, select theCommunication Portused for your radio and connect to the RF407-series radio.

  4. On theMaintab, set theActive InterfacetoUSBorRS-232(depending on how your computer will be connected to the RF407-series radio).

  5. Apply the changes.

  6. Connect the RF407-Series radio to the computer communication port selected in the previous step.

Setting up communications between the RF407-Series data logger and the computer

These instructions provide an easy way to set up communications between the RF407-series data logger and the computer connected to the RF407-series radio (as configured in previous instructions). Follow these instructions multiple times to set up multiple data loggers. In this case, each data logger must be given a unique PakBus address (seePakBus communicationsfor more information). For more complicated networks, it is recommended that you useClosedNetwork PlannerCampbell Scientific software designed to help set up datal oggers in PakBus networks so that they can communicate with each other and the LoggerNet server. For more information, see //m.ocbeachreo.com/loggernet..

  1. Supply 12 VDC power to the data logger.

  2. Ensure the data logger antenna is connected.

  3. Using data logger support software, launch the EZSetup Wizard and add the data logger.

  4. ClickNext.

  5. Select the CR300 Series从列表中数据记录器,da输入一个名字ta logger (for example, a site or project name), and clickNext.

  6. If prompted, select theDirect Connectconnection type and clickNext.

  7. Select the communication port used to communicate with the RF407-series radio from theCOM Portlist. (Note that the RF407-series radio to RF407-series data logger link is not indicated in theLoggerNetSetup Standard View.)

  8. Accept the default value of00 secondsin theCOM Port Communication Delay- this box is used to allow time for hardware devices to "wake up" and negotiate a communications link. ClickNext.

  9. In the previous instruction "Configuring a Connection to an RF407-Series Radio," you were asked to select an active interface option of USB or RS-232. If you selected USB as the active interface for the radio, you do not need to select a baud rate. If you selected RS-232, set the baud rate to the one chosen during that step. The radio's default baud rate is 115200. TheClosedPakBus® A proprietary communication protocol developed by Campbell Scientific to facilitate communications between Campbell Scientific devices. Similar in concept to IP (Internet Protocol), PakBus is a packet-switched network protocol with routing capabilities. A registered trademark of Campbell Scientific, Inc.address must match the hardware settings for your data logger. The defaultPakBus Addressis1.

  10. ClickNext.

  11. By default, the data logger does not use a security code or a PakBus encryption key. Therefore, theSecurity Codecan be left at0and thePakBus Encryption Keycan be left blank. If either setting has been changed, enter the new code or key. SeeData logger securityfor more information.

  12. ClickNext.

  13. Review theCommunication Setup Summary. If you need to make changes, click thePreviousbutton to return to a previous window and change the settings.

Setup is now complete, and the EZSetup Wizard allows you to clickFinishor clickNextto test communications, set the data logger clock, and send a program to the data logger. SeeTesting communications with EZSetupfor more information.

If you experience network communications problems, seeTroubleshooting Radio Communicationsfor assistance.